ABB RELION REX640 Technical Manual page 1278

Protection and control
Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

Protection related functions
Figure 724: Fault occurs at one of the parallel lines. CS=carrier signal sending, CR=carrier signal
receiving
The faulty feeder (Feeder 1) is not simultaneously tripped at both ends and, for
example, the circuit breaker closer to the fault at Relay B1 may be tripped faster than
the breaker at bus A. As a result, when the breaker at Relay B1 opens, the direction of
the fault current at the healthy feeder (Feeder 2) is reversed.
Figure 725: Circuit breaker at Relay B1 opens and creates a current reversal condition. CS=carrier signal
sending, CR=carrier signal receiving
Relay A2 still sends the CS signal because of the reset time delay of the forward
direction residual overcurrent function of Relay A2. When Relay B2 starts to
recognize the fault in the forward direction, Relay B2 can malfunction and trip the
breaker of the healthy feeder.
This problem can be solved using the reverse directional residual overcurrent
function to recognize the fault in reverse direction and temporarily block the
operation of the scheme communication logic due to the current reversal condition.
This is used in RCRWPSCH.
1278
1MRS759142 F
REX640
Technical Manual

Advertisement

Table of Contents
loading

Table of Contents