Protection functions
Characteristic
Operate time accuracy in definite
time mode
Operate time accuracy in IDMT
mode
Suppression of harmonics
4.12.4
Shunt capacitor bank switching resonance protection,
current based, SRCPTOC (ANSI 55ITHD)
4.12.4.1
Identification
Function description
Shunt capacitor bank switching res-
onance protection, current based
4.12.4.2
Function block
Figure 638: Function block symbol
4.12.4.3
Functionality
The shunt capacitor bank switching resonance protection, current based, function
SRCPTOC is used for detecting three-phase resonance caused by capacitor
switching or topology changes in the network. The operating characteristic is a
definite time (DT).
SRCPTOC contains a blocking functionality. It is possible to block function outputs,
timers or the function itself.
4.12.4.4
Analog input configuration
SRCPTOC has one analog group input which must be properly configured.
Table 1087: Analog inputs
Input
I3P
1142
See the preprocessing function blocks in this document for the possible
signal sources.
Value
1 % of the theoretical value or ±20 ms
5 % of the theoretical value or ±20 ms
DFT: -50 dB at f = n × f
, where n = 2,3,4,5,..
n
IEC 61850
IEC 60617
identification
identification
SRCPTOC
TD>
Description
Three-phase currents
1MRS759142 F
ANSI/IEEE C37.2
device number
55ITHD
REX640
Technical Manual