ABB RELION REX640 Technical Manual page 1103

Protection and control
Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

1MRS759142 F
4.10.7.2
STTPMSU Output signals
Table 1037: STTPMSU Output signals
Name
OPR_IIT
OPR_STALL
MOT_START
LOCK_START
4.10.8
STTPMSU Settings
Table 1038: STTPMSU Group settings (Basic)
Parameter
Values (Range)
Motor start-up A
1.0...10.0
Motor start-up
1...80
time
Lock rotor time
2...120
Str over delay time
0...60000
Table 1039: STTPMSU Group settings (Advanced)
Parameter
Values (Range)
Start detection A
0.1...10.0
Table 1040: STTPMSU Non group settings (Basic)
Parameter
Operation
Operation
mode
Table continues on the next page
REX640
Technical Manual
Type
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
Unit
Step
xIn
0.1
s
1
s
1
ms
1
Unit
Step
xIn
0.1
Values
Unit
(Range)
1=on
5=off
1=IIt
2=IIt, CB
3=IIt + stall
4=IIt + stall,
CB
Protection functions
Description
Operate/trip signal for ther-
mal stress.
Operate/trip signal for stall-
ing protection.
Signal to show that motor
startup is in progress
Lock out condition for restart
of motor.
Default
2.0
5
10
100
Default
1.5
Step
Default
1=on
1=IIt
Description
Motor starting cur-
rent
Motor starting time
Permitted stalling
time
Time delay to check
for completion of
motor startup peri-
od
Description
Current value for
detecting starting
of motor.
Description
Operation
Off / On
Motor start-
up operation
mode
1103

Advertisement

Table of Contents
loading

Table of Contents