1MRS759142 F
The DGMGAPC function is mainly used to protect the diesel generator from
the over/under fueling of the diesel engines and over/under excitation of the
generators. These faults are not easily detected by the traditional protection relay
algorithms, which can result in healthy generators behaving abnormally in an
attempt to maintain the system voltage and frequency within acceptable limits.
This can lead to a cascade fault in which all the healthy generators are disconnected,
leaving only the faulty unit running. Without the healthy generators to maintain
the frequency and voltage, the faulty generator will also be tripped, resulting in a
complete blackout of that part of the industrial network.
The DGMGAPC function identifies the existing network topology and the generators
are compared with the expected behavior corresponding to their operation mode or
with other generators with in the network.
Two algorithms are used to detect fueling and excitation faults, namely, Correlation
and Voting algorithms. The Correlation algorithm compares the generator behavior
with the set operation mode of the governor. If the local generator is deviating
significantly then it is identified as faulty. The Voting algorithm works on the
assumption that, generators share the load similarly. Hence a generator is identified
as faulty, if the local generation is moving significantly away from the rest of the
generators in the network. Any generator identified as faulty will not be used in
either of the algorithms.
Real and reactive power for the local generator is obtained from power
measurement function PEMMXU and for the network generator over GOOSE. As
an example, a part of application configuration with two generators is shown in
Figure 802
is obtained from PEMMXU and Generator2 is the network generator whose real and
reactive power are obtained over GOOSE.
REX640
Technical Manual
. Here, Generator1 is the local generator whose real and reactive power
Condition monitoring functions
1419