ABB RELION REX640 Technical Manual page 1324

Protection and control
Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

Supervision functions
6.3.8.4
HZCCASPVC Output signals
Table 1257: HZCCASPVC Output signals
Name
ALARM
6.3.8.5
HZCCBSPVC Output signals
Table 1258: HZCCBSPVC Output signals
Name
ALARM
6.3.8.6
HZCCCSPVC Output signals
Table 1259: HZCCCSPVC Output signals
Name
ALARM
6.3.9
Settings
6.3.9.1
HZCCASPVC Settings
Table 1260: HZCCASPVC Non group settings (Basic)
Parameter
Values (Range)
Operation
1=on
5=off
Start value
1.0...100.0
Alarm delay time
100...300000
Alarm output mode 1=Non-latched
3=Lockout
Table 1261: HZCCASPVC Non group settings (Advanced)
Parameter
Values (Range)
Reset delay time
0...60000
Measurement
2=DFT
mode
3=Peak-to-Peak
6.3.9.2
HZCCBSPVC Settings
1324
Type
BOOLEAN
Type
BOOLEAN
Type
BOOLEAN
Unit
Step
%In
0.1
ms
10
Unit
Step
ms
10
1MRS759142 F
Description
Alarm output
Description
Alarm output
Description
Alarm output
Default
Description
1=on
Operation Off / On
10.0
Start value, per-
centage of the
nominal current
3000
Alarm delay time
3=Lockout
Select the opera-
tion mode for
alarm output
Default
Description
20
Reset delay time
2=DFT
Selects used meas-
urement mode
Technical Manual
REX640

Advertisement

Table of Contents
loading

Table of Contents