1MRS759142 F
Table 1045:
Operation Mode
"Under"
"Over"
The
if the input signal is slightly above or below the
hysteresis area, the start condition has to be fulfilled again and it is not sufficient
for the signal to only return to the hysteresis area. If the ENA_ADD input is activated,
the threshold value of the internal comparator is the sum of the
and
increased or decreased depending on the sign and value of the
setting.
Timer
Once activated, the timer activates the START output. The time characteristic is
according to DT. When the operation timer has reached the value set by
delay time , the OPERATE output is activated. If the starting condition disappears
before the module operates, the reset timer is activated. If the reset timer reaches
the value set by
is deactivated.
The timer calculates the start duration value START_DUR, which indicates the
percentage ratio of the start situation and the set operation time. The value is
available in the monitored data view.
Blocking logic
There are three operation modes in the blocking function. The operation modes
are controlled by the BLOCK input and the global setting in Configuration >
System > Blocking mode which selects the blocking mode. The BLOCK input can
be controlled by a binary input, a horizontal communication input or an internal
signal of the protection relay's program. The influence of the BLOCK signal activation
is preselected with the global setting
The
mode, the operation timer is frozen to the prevailing value, but the OPERATE output
is not deactivated when blocking is activated. In the "Block all" mode, the whole
function is blocked and the timers are reset. In the "Block OPERATE output" mode,
the function operates normally but the OPERATE output is not activated.
4.11.5
Application
The function block can be used for any general analog signal protection, either
underprotection or overprotection. The setting range is wide, allowing various
protection schemes for the function. Thus, the absolute hysteresis can be set to
a value that suits the application.
REX640
Technical Manual
Operation mode types
Absolute hysteresis setting can be used for preventing unnecessary oscillations
Start value settings. The resulting threshold value for the comparator can be
Reset delay time , the operation timer resets and the START output
Blocking mode setting has three blocking methods. In the "Freeze timers"
Description
If the input signal
AI_VALUE
the set value of the "Start value" setting, the
level detector enables the timer module.
If the input signal
AI_VALUE
Start value setting, the level de-
value of the
tector enables the timer module.
Start value setting. After leaving the
Blocking mode .
Protection functions
is lower than
exceeds the set
Start value Add
Start value Add
Operate
1107