ABB RELION REX640 Technical Manual page 1365

Protection and control
Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

1MRS759142 F
7.1.5.4
Operation counter
The operation counter subfunction calculates the number of breaker operation
cycles. The opening and closing operations are both included in one operation cycle.
The operation counter value is updated after each opening operation.
The operation of the subfunction can be described with a module diagram. All the
modules in the diagram are explained in the next sections.
Figure 777: Functional module diagram for counting circuit breaker operations
Operation counter
The operation counter counts the number of operations based on the state change
of the binary auxiliary contacts inputs POSCLOSE and POSOPEN.
The number of operations NO_OPR is available in the monitored data view on
the LHMI or through tools via communications. The old circuit breaker operation
counter value can be taken into use by writing the value to the
parameter and by setting the parameter
WHMI or LHMI.
Alarm limit check
The OPR_ALM operation alarm is generated when the number of operations exceeds
the value set with the
of operations increases further and exceeds the limit value set with the
number setting, the OPR_LO output is activated.
The binary outputs OPR_LO and OPR_ALM are deactivated when the BLOCK input is
activated.
7.1.5.5
Accumulation of I y t
Accumulation of the I
The operation of the module can be described with a module diagram. All the
modules in the diagram are explained in the next sections.
REX640
Technical Manual
CB wear values in the clear menu from
Alarm Op number threshold setting. However, if the number
y
t module calculates the accumulated energy.
Condition monitoring functions
Counter initial Val
Lockout Op
1365

Advertisement

Table of Contents
loading

Table of Contents