ABB RELION REX640 Technical Manual page 1218

Protection and control
Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

Protection related functions
5.7.8
Signals
5.7.8.1
SCEFRFLO Input signals
Table 1157: SCEFRFLO Input signals
Name
I3P
U3P
URES
BLOCK
TRIGG_REC
TRIGG_XC0F
TRIGG_T
5.7.8.2
SCEFRFLO Output signals
Table 1158: SCEFRFLO Output signals
Name
ALARM
5.7.9
SCEFRFLO Settings
Table 1159: SCEFRFLO Group settings (Basic)
Parameter
Values (Range)
Flt Loc Det mode
2=Non-comp
1=Comp, switched
R
Z Max phase load
1.0...10000.0
Ph leakage Ris
20...1000000
Ph capacitive React 10...1000000
R1 line section A
0.000...1000.000
Table continues on the next page
1218
Type
SIGNAL
SIGNAL
SIGNAL
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
Type
BOOLEAN
Unit
Step
ohm
0.1
ohm
1
ohm
1
ohm / pu
0.001
Default
Description
-
Three-phase currents
-
Three-phase voltages
-
Residual voltage
0=False
Signal for blocking
the triggering
0=False
Distance calculation
triggering signal
0=False
XC0F calculation trig-
gering signal
0=False
Start calculation se-
quence for compen-
sation network
Description
Fault location alarm signal
Default
2=Non-comp
80.0
210000
7000
1.000
1MRS759142 F
Description
Fault location de-
tection mode
Impedance per
phase of max.
load, overcurr./un-
der-imp., PSL
Line PhE leakage
resistance in pri-
mary ohms
Line PhE capaci-
tive reactance in
primary ohms
Positive sequence
line resistance, line
section A
REX640
Technical Manual