This function contains a blocking functionality. It is possible to block the function
outputs, reset timer or the function itself.
4.7.4.4
Analog channel configuration
UZPDIS has two analog group inputs which all must be properly configured.
Table 958: Analog inputs
Input
I3P
U3P
There are a few special conditions which must be noted with the configuration.
Table 959: Special conditions
Condition
U3P connected to real measurements
Improper analog channel configuration causes a validation error if the analog
channels are not completely configured or they do not match with certain settings.
For troubleshooting, check the contents of this chapter and also the preprocessing
blocks in this document. The configuration can be written to the protection relay
once the mismatch is corrected.
4.7.4.5
Operation principle
The function can be enabled and disabled with the
corresponding parameter values are "On" and "Off".
The operation of UZPDIS can be described with a module diagram. All the modules
in the diagram are explained in the next sections.
REX640
Technical Manual
See the preprocessing function blocks in this document for the possible
signal sources.
Protection functions
Description
Three-phase currents
Three-phase voltages
Description
The function can work with one voltage chan-
Phase Sel for Z Clc set to "AB",
nel connected (
"BC" or "CA"), if the setting
mode is set to "1Phase-to-phase".
The function requires that at least two (the
third voltage will be derived) or  all three
voltage channels are connected if
Meas mode is set to "3Phase-to-phase".
Operation setting. The
Impedance Meas
Impedance
1027