Protection related functions
Table 1227: DNZSRDIR Non group settings (Advanced)
Parameter
Values (Range)
Reset delay time
0...60000
Min operate current 1.0...100.0
Min operate volt-
1.0...100.0
age
Pol reversal
0=False
1=True
5.15.9
DNZSRDIR Monitored data
Table 1228: DNZSRDIR Monitored data
Name
Type
ANGLE_RCA
FLOAT32
DNZSRDIR
Enum
5.16
Load blinder LBRDOB (ANSI 21LB)
5.16.1
Identification
Function description
Load blinder
5.16.2
Function block
Figure 734: Function block
1294
Unit
Step
ms
1
%In
0.1
%Un
0.1
Values (Range)
-180.00...180.00
1=on
2=blocked
3=test
4=test/blocked
5=off
IEC 61850
identification
LBRDOB
Default
20
10.0
30.0
0=False
Unit
Description
deg
Angle between operat-
ing angle and charac-
teristic angle
Status
IEC 60617
ANSI/IEEE
identification
identification
LB
21LB
1MRS759142 F
Description
Reset delay time
Minimum operating
current
Minimum operating
voltage
Rotate polarizing
quantity
REX640
Technical Manual