Protection related functions
5.8.7.1
CVPSOF Input signals
Table 1169: CVPSOF Input signals
Name
I3P
U3P
BLOCK
CB_CL_CMD
START
START_DLYD
5.8.7.2
CVPSOF Output signals
Table 1170: CVPSOF Output signals
Name
OPERATE
5.8.8
CVPSOF Settings
Table 1171: CVPSOF Non group settings (Basic)
Parameter
Values (Range)
Operation
1=on
5=off
Table 1172: CVPSOF Non group settings (Advanced)
Parameter
Values (Range)
Operation mode
1=Start
2=Current&voltage
3=Both
SOTF initialization
1=SwitchCommand
-2=Voltage or
SwitchCmd
-3=Current or
SwitchCmd
-4=Cur&Vol or
SwitchCmd
Table continues on the next page
1228
Type
SIGNAL
SIGNAL
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
Type
BOOLEAN
Unit
Step
Unit
Step
Default
Description
-
Three-phase currents
-
Three-phase voltages
0=False
Block signal for acti-
vating the blocking
mode
0=False
External enabling of
SOTF by CB close
command
0=False
Start from function
to be accelerated by
SOTF
0=False
Start from function
to be accelerated
with delay by SOTF
Description
Operate
Default
1=on
Default
3=Both
-2=Voltage or
SwitchCmd
1MRS759142 F
Description
Operation Off / On
Description
Mode of operation
of SOTF Function
Switch onto fault
initialization
REX640
Technical Manual