ABB RELION REX640 Technical Manual page 1061

Protection and control
Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

1MRS759142 F
DUPPDPR Output signals
Table 993: DUPPDPR Output signals
Name
OPERATE
START
4.8.1.8
DUPPDPR Settings
Table 994: DUPPDPR Group settings (Basic)
Parameter
Values (Range)
Start value
0.01...2.00
Operate delay time
40...300000
Table 995: DUPPDPR Non group settings (Basic)
Parameter
Values (Range)
Operation
1=on
5=off
Table 996: DUPPDPR Non group settings (Advanced)
Parameter
Values (Range)
Measurement
1=PhsA, PhsB, PhsC
mode
2=Arone
3=Pos Seq
4=PhsAB
5=PhsBC
6=PhsCA
7=PhsA
8=PhsB
9=PhsC
Reset delay time
0...60000
Pol reversal
0=False
1=True
Disable time
0...60000
4.8.1.9
DUPPDPR Monitored data
Table 997: DUPPDPR Monitored data
Name
Type
START_DUR
FLOAT32
P
FLOAT32
Q
FLOAT32
S
FLOAT32
Table continues on the next page
REX640
Technical Manual
Type
BOOLEAN
BOOLEAN
Unit
Step
xSn
0.01
ms
10
Unit
Step
Unit
Step
ms
10
ms
1000
Values (Range)
0.00...100.00
-160.000...160.000
-160.000...160.000
0.000...160.000
Protection functions
Description
Operate
Start
Default
0.10
40
Default
1=on
Default
3=Pos Seq
20
0=False
0
Unit
Description
%
Ratio of start time / op-
erate time
xSn
Active power
xSn
Reactive power
xSn
Apparent power
Description
Start value
Operate delay time
Description
Operation On/Off
Description
Selection of power
calculation method
Reset delay time
Reverse the defini-
tion of the power
direction
Additional wait
time after CB clos-
ing
1061

Advertisement

Table of Contents
loading

Table of Contents