ABB RELION REX640 Technical Manual page 1325

Protection and control
Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

1MRS759142 F
Table 1262: HZCCBSPVC Non group settings (Basic)
Parameter
Values (Range)
Operation
1=on
5=off
Start value
1.0...100.0
Alarm delay time
100...300000
Alarm output mode 1=Non-latched
3=Lockout
Table 1263: HZCCBSPVC Non group settings (Advanced)
Parameter
Values (Range)
Reset delay time
0...60000
Measurement
2=DFT
mode
3=Peak-to-Peak
6.3.9.3
HZCCCSPVC Settings
Table 1264: HZCCCSPVC Non group settings (Basic)
Parameter
Values (Range)
Operation
1=on
5=off
Start value
1.0...100.0
Alarm delay time
100...300000
Alarm output mode 1=Non-latched
3=Lockout
Table 1265: HZCCCSPVC Non group settings (Advanced)
Parameter
Values (Range)
Reset delay time
0...60000
Measurement
2=DFT
mode
3=Peak-to-Peak
6.3.10
Monitored data
6.3.10.1
HZCCASPVC Monitored data
Table 1266: HZCCASPVC Monitored data
Name
Type
HZCCASPVC
Enum
REX640
Technical Manual
Unit
Step
%In
0.1
ms
10
Unit
Step
ms
10
Unit
Step
%In
0.1
ms
10
Unit
Step
ms
10
Values (Range)
1=on
2=blocked
3=test
4=test/blocked
Supervision functions
Default
1=on
10.0
3000
3=Lockout
Default
20
2=DFT
Default
1=on
10.0
3000
3=Lockout
Default
20
2=DFT
Unit
Description
Status
Description
Operation Off / On
Start value, per-
centage of the
nominal current
Alarm delay time
Select the opera-
tion mode for
alarm output
Description
Reset delay time
Selects used meas-
urement mode
Description
Operation Off / On
Start value, per-
centage of the
nominal current
Alarm delay time
Select the opera-
tion mode for
alarm output
Description
Reset delay time
Selects used meas-
urement mode
1325