Improper analog channel configuration causes a validation error if the analog
channels are not completely configured or they do not match with certain settings.
For troubleshooting, check the contents of this chapter and also the preprocessing
blocks in this document. The configuration can be written to the protection relay
once the mismatch is corrected.
4.12.4.5
Operation principle
The function can be enabled and disabled with the
corresponding parameter values are "On" and "Off".
The operation of SRCPTOC can be described by using a module diagram. All the
modules in the diagram are explained in the next sections.
RESO_IN
Figure 639: Functional module diagram
Resonance current calculation
This module calculates the resonance current per phase set as per setting
harmonic Num . The resonance current for phase A is calculated with the equation.
I RESO A
_
I
RMS_A
I
DC_A
I_A
I
K_A
I_RESO_A
The resonance current is calculated through the filter implementation. The DC and
fundamental components are removed by passing the total RMS current through
the High pass filter. The K
High pass filter output through the K
REX640
Technical Manual
I_A
I_B
I3P
I_C
BLOCK
2
_
I
=
RMS A
_
RMS value of current in phase A (contains up to 11
DC-component in phase A current
Fundamental component in phase A current
th
K
harmonic component in phase A current, K is defined by setting
harmonic Num
Calculated resonance current for phase A
Resonance
Level
current
detector 1
calculation
Level
detector 2
Blocking
logic
2
2
2
I
I
I
1
_
A
DC A
_
K A
_
th
harmonic component is removed by passing the
th
harmonic Band stop filter. The magnitude
Protection functions
Operation setting. The
Timer 1
t
ALARM
Timer 2
t
OPERATE
(Equation 289)
th
harmonic)
Tuning
Tuning
1143