1MRS759142 F
Parameter
Values (Range)
X1 line section A
0.000...1000.000
R0 line section A
0.000...1000.000
X0 line section A
0.000...1000.000
Line Len section A
0.000...1000.000
Table 1160: SCEFRFLO Group settings (Advanced)
Parameter
Values (Range)
High alarm Dis limit 0.000...1.000
Low alarm Dis limit 0.000...1.000
Equivalent load Dis
0.00...1.00
R1 line section B
0.000...1000.000
X1 line section B
0.000...1000.000
R0 line section B
0.000...1000.000
X0 line section B
0.000...1000.000
Line Len section B
0.000...1000.000
R1 line section C
0.000...1000.000
X1 line section C
0.000...1000.000
R0 line section C
0.000...1000.000
X0 line section C
0.000...1000.000
Line Len section C
0.000...1000.000
Table 1161: SCEFRFLO Non group settings (Basic)
Parameter
Values (Range)
Operation
1=on
5=off
Phase voltage Meas 1=Accurate
2=Ph-to-ph without
Uo
Calculation Trg
1=Internal
mode
2=External
REX640
Technical Manual
Unit
Step
ohm / pu
0.001
ohm / pu
0.001
ohm / pu
0.001
pu
0.001
Unit
Step
pu
0.001
pu
0.001
0.01
ohm / pu
0.001
ohm / pu
0.001
ohm / pu
0.001
ohm / pu
0.001
pu
0.001
ohm / pu
0.001
ohm / pu
0.001
ohm / pu
0.001
ohm / pu
0.001
pu
0.001
Unit
Step
Protection related functions
Default
Description
1.000
Positive sequence
line reactance, line
section A
4.000
Zero sequence line
resistance, line sec-
tion A
4.000
Zero sequence line
reactance, line sec-
tion A
0.000
Line length, section
A
Default
Description
0.000
High alarm limit for
calculated distance
0.000
Low alarm limit for
calculated distance
0.50
Equivalent load dis-
tance when EF al-
gorithm equals to
load modelling
1.000
Positive sequence
line resistance, line
section B
1.000
Positive sequence
line reactance, line
section B
4.000
Zero sequence line
resistance, line sec-
tion B
4.000
Zero sequence line
reactance, line sec-
tion B
0.000
Line length, section
B
1.000
Positive sequence
line resistance, line
section C
1.000
Positive sequence
line reactance, line
section C
4.000
Zero sequence line
resistance, line sec-
tion C
4.000
Zero sequence line
reactance, line sec-
tion C
0.000
Line length, section
C
Default
Description
1=on
Operation Off / On
1=Accurate
Phase voltage
measurement prin-
ciple
2=External
Trigger mode
for distance calcu-
lation
1219