ABB RELION REX640 Technical Manual page 1155

Protection and control
Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

1MRS759142 F
CNUPTOV Input signals
Table 1096: CNUPTOV Input signals
Name
U3P
URES
UNEUT
BLOCK
CNUPTOV Output signals
Table 1097: CNUPTOV Output signals
Name
OPERATE
START
4.12.5.9
CNUPTOV Settings
Table 1098: CNUPTOV Group settings (Basic)
Parameter
Values (Range)
Start value
0.01...1.00
Operate delay time
100...300000
Table 1099: CNUPTOV Non group settings (Basic)
Parameter
Values (Range)
Operation
1=on
5=off
Table 1100: CNUPTOV Non group settings (Advanced)
Parameter
Values (Range)
Reset delay time
0...60000
4.12.5.10
CNUPTOV Monitored data
Table 1101: CNUPTOV Monitored data
Name
Type
START_DUR
FLOAT32
U_AMPL_RES
FLOAT32
Table continues on the next page
REX640
Technical Manual
Type
SIGNAL
SIGNAL
SIGNAL
BOOLEAN
Type
BOOLEAN
BOOLEAN
Unit
Step
xUn
0.01
ms
100
Unit
Step
Unit
Step
ms
1
Values (Range)
0.00...100.00
0.00...5.00
Protection functions
Default
Description
-
Three-phase voltages
-
Residual voltage
-
Analog input
0=False
Block signal for acti-
vating the blocking
mode
Description
Operate
Start
Default
0.01
100
Default
1=on
Default
20
Unit
%
xUn
Description
Start value
Operate delay time
Description
Operation Off / On
Description
Reset delay time
Description
Ratio of start time / op-
erate time
Magnitude of capaci-
tor terminal open delta
voltage (either calcula-
ted or derived)