Supervision functions
Figure 745: Functional module diagram
Differential current monitoring
Differential current monitoring supervises the difference between the summed
phase currents I_A, I_B and I_C and the reference current I_REF.
The current operating characteristics can be selected with the
When the highest phase current is less than 1.0 × In, the differential current limit is
defined with
differential current limit is calculated with the equation.
MAX I A I B I C
The differential current is limited to 1.0 × In.
Figure 746: CCSPVC operating characteristics
When the differential current I_DIFF is in the operating region, the FAIL output is
activated.
1312
I_A
I_B
I3P
I_C
Io
IRES
BLOCK
Start value . When the highest phase current is more than 1.0 × In, the
( _ , _ , _ ) ×
Start value
Timer
Differential
t
current
monitoring
1MRS759142 F
FAIL
ALARM
Start value setting.
(Equation 315)
REX640
Technical Manual