ABB RELION REX640 Technical Manual page 1478

Protection and control
Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

Measurement functions
Name
U1_INST
U0_INST
8.1.12.6
VSMSQI Settings
Table 1425: VSMSQI Non group settings (Basic)
Parameter
Values (Range)
Operation
1=on
5=off
Ps Seq V Hi high
0.00...4.00
Lim
Ps Seq V high limit
0.00...4.00
Ps Seq V low limit
0.00...4.00
Ps Seq V low low
0.00...4.00
Lim
Ps Seq V deadband 100...100000
Ng Seq V Hi high
0.00...4.00
Lim
Ng Seq V High limit 0.00...4.00
Ng Seq V low limit
0.00...4.00
Ng Seq V low low
0.00...4.00
Lim
Ng Seq V deadband 100...100000
Table continues on the next page
1478
Type
FLOAT32
FLOAT32
Unit
Step
xUn
0.01
xUn
0.01
xUn
0.01
xUn
0.01
1
xUn
0.01
xUn
0.01
xUn
0.01
xUn
0.01
1
1MRS759142 F
Description
Positive sequence voltage
amplitude, instantaneous val-
ue (kV)
Zero sequence voltage am-
plitude, instantaneous value
(kV)
Default
Description
1=on
Operation Off / On
1.40
High alarm voltage
limit for positive
sequence voltage
1.20
High warning volt-
age limit for posi-
tive sequence volt-
age
0.00
Low warning volt-
age limit for posi-
tive sequence volt-
age
0.00
Low alarm voltage
limit for positive
sequence voltage
10000
Deadband configu-
ration value for
positive sequence
voltage for inte-
gral calculation.
(percentage of dif-
ference between
min and max as
0,001 % s)
0.20
High alarm voltage
limit for negative
sequence voltage
0.05
High warning volt-
age limit for nega-
tive sequence volt-
age
0.00
Low warning volt-
age limit for nega-
tive sequence volt-
age
0.00
Low alarm voltage
limit for negative
sequence voltage
10000
Deadband configu-
ration value for
negative sequence
voltage for inte-
gral calculation.
(percentage of dif-
ference between
min and max as
0,001 % s)
Technical Manual
REX640

Advertisement

Table of Contents
loading

Table of Contents