ABB RELION REX640 Technical Manual page 1132

Protection and control
Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

Protection functions
4.12.3.4
Analog channel configuration
HCUBPTOC has two analog group inputs which must be properly configured.
Table 1076: Analog inputs
Input
I3P1
I3P2
Improper analog channel configuration causes a validation error if the analog
channels are not completely configured or they do not match with certain settings.
For troubleshooting, check the contents of this chapter and also the preprocessing
blocks in this document. The configuration can be written to the protection relay
once the mismatch is corrected.
4.12.3.5
Operation principle
The function can be enabled and disabled with the Operation setting. The
corresponding parameter values are "On" and "Off".
The three-phase current unbalance protection for shunt capacitor banks operates
on the DFT measurement mode. The operation of HCUBPTOC can be described by
using a module diagram. All the modules in the diagram are explained in the next
sections.
BLOCK
Figure 633: Function module diagram
Natural unbalance compensation
In the three-phase H-bridge-connected shunt capacitor bank configuration, the
unbalance currents I_UNB_A, I_UNB_B and I_UNB_C are measured at the common
points of the H-bridge.
1132
See the preprocessing function blocks in this document for the possible
signal sources.
I_A
I3P1
I_UNB_A
I_UNB_B
I3P2
I_UNB_C
Description
Three-phase currents
Three-phase unbalance currents
Natural
Level
unbalance
compens-
detector 1
ation
Blocking
logic
Level
detector 2
1MRS759142 F
Timer 1
t
OPERATE
START
t
Timer 2
t
ALARM
REX640
Technical Manual