ABB RELION REX640 Technical Manual page 1012

Protection and control
Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

Protection functions
4.7.2.6
Application
Out of step protection functions detect stable power swings and out of step
conditions based on the fact that the voltage/current variation during a power
swing is slow compared to the step change during a fault. Both faults and
power swings may cause the measured impedance to enter into the operating
characteristic of a distance relay element. The apparent impedance moves from the
pre-fault value to a fault value in a very short time, a few milliseconds, during a fault
condition. However, the rate of change of the impedance is much slower during a
power swing or out of step condition than during a fault depending on the slip
frequency of the out of step. The impedance measurement should not be used by
itself to distinguish between a fault condition and an out of step condition from a
phase fault. The fundamental method for discriminating between faults and power
swings is to track the rate of change of the measured impedance.
The function measures the rate of change of the impedance using two impedance
measurement elements known as blinders together with a timing device. If the
measured impedance stays between the blinders for a predetermined time, the
function declares a power swing condition and asserts an output that can be
used to block the distance protection. However, if the impedance passes the inner
blinder and exits on the other side of the mho characteristics (that is, the resistive
component of impedance has opposite sign as at the time of point of entry) an out
of step operate is issued by the function.
detection.
B
-R
Figure 562: Example of out of step detection
The shaded region indicates a fault zone in a distance protection function. For curve
A, the impedance moves into the out of step zone and leaves slowly, indicating the
occurrence of a swing that quickly stabilizes. For curve B, the impedance moves
slowly into the out of step zone and exits the zone indicating that the network is
becoming unstable. For curve C, impedance rapidly moves into, and remains in, the
fault zone indicating an actual fault and not an out of step condition.
4.7.2.7
Signals
1012
Figure 562
X
C
-X
1MRS759142 F
gives an example of out of step
A
R
Technical Manual
REX640

Advertisement

Table of Contents
loading

Table of Contents