Condition monitoring functions
Name
CDRP_F_SET
GEN1_DATA
GEN2_DATA
GEN3_DATA
GEN4_DATA
GEN5_DATA
GEN6_DATA
GEN7_DATA
GEN8_DATA
BLOCK
GCB_CLOSED
GCB_OPEN
TIE_A_CLOSED
TIE_A_OPEN
TIE_B_CLOSED
TIE_B_OPEN
GOV_MOD_ISOC
GOV_MOD_DRP
GOV_MOD_CDRP
GOV_MOD_BASE
Table continues on the next page
1422
Type
Default
FLOAT32
0.0
INT32
0
INT32
0
INT32
0
INT32
0
INT32
0
INT32
0
INT32
0
INT32
0
BOOLEAN
0=False
BOOLEAN
0=False
BOOLEAN
0=False
BOOLEAN
0=False
BOOLEAN
0=False
BOOLEAN
0=False
BOOLEAN
0=False
BOOLEAN
0=False
BOOLEAN
0=False
BOOLEAN
0=False
BOOLEAN
0=False
1MRS759142 F
Description
Compensated droop
no load set point fre-
quency from PMS
Data received from
network generator 1
Data received from
network generator 2
Data received from
network generator 3
Data received from
network generator 4
Data received from
network generator 5
Data received from
network generator 6
Data received from
network generator 7
Data received from
network generator 8
Block input to block
all binary outputs
Local generator cir-
cuit breaker closed
position status
Local generator cir-
cuit breaker open po-
sition status
Adjacent tie breaker A
closed position
Adjacent tie breaker A
open position
Adjacent tie breaker B
closed position
Adjacent tie breaker B
open position
Governor isochronous
mode status
Governor droop mode
status
Governor compensa-
ted droop mode sta-
tus
Governor base load
mode status
REX640
Technical Manual