ABB RELION REX640 Technical Manual page 1373

Protection and control
Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

1MRS759142 F
7.1.7.2
SSCBR Output signals
Table 1311: SSCBR Output signals
Name
TRV_T_OP_ALM
TRV_T_CL_ALM
SPR_CHR_ALM
OPR_ALM
OPR_LO
IPOW_ALM
IPOW_LO
CB_LIFE_ALM
MON_ALM
PRES_ALM
PRES_LO
OPENPOS
INVALIDPOS
CLOSEPOS
7.1.8
SSCBR Settings
Table 1312: SSCBR Non group settings (Basic)
Parameter
Values (Range)
Operation
1=on
5=off
Acc stop current
5.00...500.00
Open alarm time
0...200
Close alarm time
0...200
Spring charge time
0...60
Table continues on the next page
REX640
Technical Manual
Type
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
Unit
Step
A
0.01
ms
10
ms
10
s
1
Condition monitoring functions
Description
CB open travel time exceeded
set value
CB close travel time exceeded
set value
Spring charging time has
crossed the set value
Number of CB operations ex-
ceeds alarm limit
Number of CB operations ex-
ceeds lockout limit
Accumulated currents power
(Iyt),exceeded alarm limit
Accumulated currents power
(Iyt),exceeded lockout limit
Remaining life of CB excee-
ded alarm limit
CB 'not operated for long
time' alarm
Pressure below alarm level
Pressure below lockout level
CB is in open position
CB is in invalid position (not
positively open or closed)
CB is in closed position
Default
Description
1=on
Operation Off / On
10.00
RMS current set-
ting below which
engy acm stops
40
Alarm level setting
for open travel time
in ms
40
Alarm level Setting
for close travel time
in ms
15
Setting of alarm
for spring charging
time of CB in s
1373