Protection functions
DOPPDPR Input signals
Table 1002: DOPPDPR Input signals
Name
I3P
U3P
BLOCK
DOPPDPR Output signals
Table 1003: DOPPDPR Output signals
Name
OPERATE
START
4.8.2.8
DOPPDPR Settings
Table 1004: DOPPDPR Group settings (Basic)
Parameter
Values (Range)
Start value
0.01...2.00
Operate delay time
40...300000
Directional mode
2=Forward
3=Reverse
Power angle
-90...90
Table 1005: DOPPDPR Non group settings (Basic)
Parameter
Values (Range)
Operation
1=on
5=off
Measurement
1=PhsA, PhsB, PhsC
mode
2=Arone
3=Pos Seq
4=PhsAB
5=PhsBC
6=PhsCA
7=PhsA
8=PhsB
9=PhsC
1070
Type
SIGNAL
SIGNAL
BOOLEAN
Type
BOOLEAN
BOOLEAN
Unit
Step
xSn
0.01
ms
10
deg
1
Unit
Step
Default
Description
-
Three-phase currents
-
Three-phase voltages
0=False
Block signal for acti-
vating the blocking
mode
Description
Operate
Start
Default
1.00
40
2=Forward
0
Default
1=on
3=Pos Seq
1MRS759142 F
Description
Start value
Operate delay time
Directional mode
Adjustable angle
for power
Description
Operation On/Off
Selection of power
calculation method