1MRS759142 F
Figure 752: Functional module diagram
Level detector
This module compares the differential current I_A to the set
module is activated if the differential current exceeds the value set in the
setting.
Timer
The time characteristic is according to DT. When the alarm timer reaches the value
set by
the module generates an alarm signal, the reset timer is activated. If the reset timer
reaches the value set by
the BLOCK signal resets the Timer and deactivates the ALARM output.
Lockout logic
HZCCxSPVC is provided with the possibility to activate a lockout for the ALARM
output depending on the
ALARM must be reset manually from the LHMI Clear menu after checking the CT
secondary circuit. In the "Non-latched" mode, the ALARM output functions normally,
that is, it resets as soon as the fault is cleared.
6.3.6
Measuring modes
The function operates on two alternative measurement modes, DFT and Peak-to-
Peak. The measurement mode is selected using the
REX640
Technical Manual
I_A
I3P
BLOCK
I_B
I3P
BLOCK
I_C
I3P
BLOCK
Alarm delay time , the ALARM output is activated. If the fault disappears before
Reset delay time , the alarm timer resets. The activation of
Alarm output mode setting. In the "Lockout" mode, the
Timer
Timer
Level
t
t
detector
Timer
Timer
Level
t
t
detector
Timer
Timer
Level
t
t
detector
Supervision functions
ALARM
ALARM
ALARM
Start value . The timer
Start value
Measurement mode setting.