Measurement functions
Parameter
Values (Range)
Table 1374: VMMXU Non group settings (Advanced)
Parameter
Values (Range)
Measurement
1=RMS
mode
2=DFT
On delay time
0...1800000
Off delay time
0...1800000
8.1.5.7
VMMXU Monitored data
Table 1375: VMMXU Monitored data
Name
Type
U12-kV:1
FLOAT32
U23-kV:1
FLOAT32
U31-kV:1
FLOAT32
UL1-kV:1
FLOAT32
UL2-kV:1
FLOAT32
UL3-kV:1
FLOAT32
BLOCK
BOOLEAN
HIGH_ALARM
BOOLEAN
HIGH_WARN
BOOLEAN
LOW_WARN
BOOLEAN
LOW_ALARM
BOOLEAN
U_INST_AB
FLOAT32
U_ANGL_AB
FLOAT32
U_DB_AB
FLOAT32
Table continues on the next page
1450
Unit
Step
Unit
Step
ms
100
ms
100
Values (Range)
0.00...4.00
0.00...4.00
0.00...4.00
0.00...5.00
0.00...5.00
0.00...5.00
0=False
1=True
0=False
1=True
0=False
1=True
0=False
1=True
0=False
1=True
0.00...4.00
-180.00...180.00
0.00...4.00
Default
Default
2=DFT
0
0
Unit
Description
xUn
Measured phase to
phase voltage ampli-
tude phase AB
xUn
Measured phase to
phase voltage ampli-
tude phase BC
xUn
Measured phase to
phase voltage ampli-
tude phase CA
xUn
Measured phase to
earth voltage amplitude
phase A
xUn
Measured phase to
earth voltage amplitude
phase B
xUn
Measured phase to
earth voltage amplitude
phase C
Block signal for all bina-
ry outputs
High alarm
High warning
Low warning
Low alarm
xUn
U12 amplitude, magni-
tude of instantaneous
value
deg
U12 angle
xUn
U12 amplitude, magni-
tude of deadband value
1MRS759142 F
Description
(percentage of dif-
ference between
min and max as
0,001 % s)
Description
Selects used meas-
urement mode
Delay the activation
of the alarm and
warning outputs
Delay the deactiva-
tion of the alarm
and warning out-
puts