ABB RELION REX640 Technical Manual page 1192

Protection and control
Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

Protection related functions
until the 10 minute time-out has passed or until the emergency start is released,
whichever takes longer.
The last change of the emergency start output signal is recorded.
5.6.7
Signals
5.6.7.1
ESMGAPC Input signals
Table 1140: ESMGAPC Input signals
Name
I3P
BLOCK
ST_EMERG_RQ
5.6.7.2
ESMGAPC Output signals
Table 1141: ESMGAPC Output signals
Name
ST_EMERG_ENA
5.6.8
ESMGAPC Settings
Table 1142: ESMGAPC Group settings (Advanced)
Parameter
Values (Range)
Motor standstill A
0.01...0.20
Table 1143: ESMGAPC Non group settings (Basic)
Parameter
Values (Range)
Operation
1=on
5=off
5.6.9
ESMGAPC Monitored data
1192
Type
SIGNAL
BOOLEAN
BOOLEAN
Type
BOOLEAN
Unit
Step
xIn
0.01
Unit
Step
Default
Description
-
Three-phase currents
0=False
Block signal for acti-
vating the blocking
mode
0=False
Emergency start in-
put
Description
Emergency start
Default
0.12
Default
1=on
1MRS759142 F
Description
Current limit to
check for motor
standstill condition
Description
Operation Off / On
REX640
Technical Manual