Figure 561: Defined zones
The impedance is continuously monitored for detecting an out of step condition.
When the impedance enters inside from the outer blinder, the out of step detection
timer is triggered. If impedance remains between outer and inner blinder for the
duration of the
enters the mho circle in zone 1, out of step blocking ( OSB) for zone 1 is detected
and output OSB is activated, or if the impedance enters the mho circle in zone 2, OSB
for zone 2 is detected and output OSB_Z2 is activated if setting
to "Yes". Both OSB and OSB_Z2 can be activated if the impedance passes through
zone 1 and zone 2 while inside the mho circle. The OSB or OSB_Z2 output deactivates
when impedance exits and remains outside the mho circle and the inner blinder for
a duration of five cycles.
Activation of the OPERATE output depends on the
available options are "Way in", "Way out", and "Adaptive". If the "Way in" option is
selected, the function triggers the delay timer after detecting an OSB condition.
When the set
When using the "Way in" option, the zone-related settings and zone slip counters are
not applicable.
If the "Way out" option is selected, after detecting an OSB condition, the function
further checks if impedance exits the outer blinder. On exiting the outer blinder, Way
out timer defined by
slip counter is incremented after the set
counter value is equal to the set number of slips in the respective enabled zone, the
OPERATE output is activated. If the swing impedance passes through both zone 1
and zone 2, only the zone 1 slip counter is incremented. The zone 2 slip counter is
incremented if the impedance passes through the Mho circle but only through the
zone 2 portion. The zone 3 slip counter is incremented if the impedance misses the
REX640
Technical Manual
Swing time setting, output SWING is activated. If the impedance
Operate delay time has elapsed, the OPERATE output is activated.
Operate delay time setting is triggered and the respective zone
Oos operate mode selected. The
Operate delay time has elapsed. If the slip
Protection functions
Zone 2 enable is set
1009