Measurement functions
Table 1439: RDRE Non group general settings (basic)
Parameter
Values (Range)
Operation
1=on
5=off
Record length
10...500
Pre-trg length
0...100
Table 1440: RDRE Non group general settings (advanced)
Parameter
Values (Range)
Operation mode
1=Saturation
2=Overwrite
Exclusion time
0...1 000 000
Storage rate
32, 16, 8
Periodic trig time
0...604 800
Stor. mode periodic 0=Waveform
1=Trend / cycle
Stor. mode manual
0=Waveform
1=Trend / cycle
Table 1441: RDRE Control data (basic)
Parameter
Values (Range)
Trig recording
0=Cancel
1=Trig
Clear recordings
0=Cancel
1=Trig
8.2.8
Monitored data
Table 1442: RDRE Monitored data
Parameter
Number of re-
cordings
Rem. amount
of rec.
Table continues on the next page
1494
Unit
Step
1
fundamental cycles 1
%
1
Unit
Step
1
ms
1
samples per funda-
mental cycle
s
10
1
1
Unit
Step
Values
Unit
(Range)
0...100
0...100
Default
1=on
50
50
Default
1
0
32
0
0
0
Default
0=Cancel
0=Cancel
Step
Default
1MRS759142 F
Description
Disturbance re-
corder on/off
Size of the record-
ing in fundamental
cycles
Length of the re-
cording preceding
the triggering
Description
Operation mode of
the recorder
The time during
which triggerings
of same type are
ignored
Storage rate of
the waveform re-
cording
Time between peri-
odic triggerings
Storage mode for
periodic triggering
Storage mode for
manual triggering
Description
Trigger the disturb-
ance recording
Clear all recordings
currently in memo-
ry
Description
Number of re-
cordings cur-
rently in
memory
Remaining
amount of re-
cordings that
REX640
Technical Manual