ABB RELION REX640 Technical Manual page 1056

Protection and control
Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

Protection functions
Table 989: Analog inputs
Input
I3P
U3P
There are a few special conditions which must be noted with the configuration.
Table 990: Special conditions
Condition
U3P connected to real measurements
Improper analog channel configuration causes a validation error if the analog
channels are not completely configured or they do not match with certain settings.
For troubleshooting, check the contents of this chapter and also the preprocessing
blocks in this document. The configuration can be written to the protection relay
once the mismatch is corrected.
4.8.1.5
Operation principle
The function can be enabled and disabled with the
corresponding parameter values are "On" and "Off".
The operation of DUPPDPR can be described using a module diagram. All the
modules in the diagram are explained in the next sections.
DISABLE
Figure 590: Functional module diagram
1056
See the preprocessing function blocks in this document for the possible
signal sources.
I_A
I_B
I3P
I_C
I
1
calculation
U_A_AB
U_B_BC
U3P
U_C_CA
U
1
BLOCK
Description
Three-phase currents
Three-phase voltages
Description
The function can work with the correspond-
ing one voltage channel connected if the
measurement mode is set to "PhsAB",
"PhsBC", "PhsCA", "PhsA", "PhsB" or "PhsC".
The function requires that at least two (the
third voltage will be derived) or all three volt-
age channels are connected for the other
measurement modes.
Directional
calculation
Power
Operation setting. The
Timer
Level
t
detector
Blocking
logic
Technical Manual
1MRS759142 F
OPERATE
START
REX640