ABB RELION REX640 Technical Manual page 1263

Protection and control
Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

1MRS759142 F
5.11.6.1
RESCPSCH Input signals
Table 1191: RESCPSCH Input signals
Name
BLOCK
BLK_CS_OPR
CSBLK
CACC
CSOR
CSUR
CR_PRM
CR_BLOCKING
CR_INTER_TR
CRG
5.11.6.2
RESCPSCH Output signals
Table 1192: RESCPSCH Output signals
Name
OPERATE
CS_PRM
CS_BLOCKING
CS_INTER_TR
Table continues on the next page
REX640
Technical Manual
Type
Default
BOOLEAN
0=False
BOOLEAN
0=False
BOOLEAN
0=False
BOOLEAN
0=False
BOOLEAN
0=False
BOOLEAN
0=False
BOOLEAN
0=False
BOOLEAN
0=False
BOOLEAN
0=False
BOOLEAN
0=False
Type
BOOLEAN
BOOLEAN
BOOLEAN
BOOLEAN
Protection related functions
Description
Block signal for acti-
vating the blocking
mode
Signal for blocking
CS and OPR in all
schemes
Reverse residual over-
current signal for Car-
rier Send
Signal to be used for
tripping by Communi-
cation Scheme
Overreaching residual
overcurrent signal for
Carrier Send
Underreaching resid-
ual overcurrent signal
for Carrier Send
Received teleprotec-
tion permissive from
the other side
Received teleprotec-
tion blocking from
the other side
Received direct trip
from the other side
Carrier guard signal
received
Description
Operate
Permissive transmitted to the
other side
Blocking transmitted to the
other side
Direct trip transmitted to the
other side
1263

Advertisement

Table of Contents
loading

Table of Contents