3 SERVOPACK Installation

3.2.2 Installation Standards

3.2.2

Installation Standards

Observe the standards for mounting SERVOPACKs in control panels, including those for the mounting
SERVOPACKs side by side in one control panel as shown in the following illustration.
• SERVOPACK Mounting Orientation
Mount the SERVOPACK vertically to the base, with the front panel (the side with the panel operator display)
facing out.
• Cooling
Refer to the following diagram and leave sufficient space for cooling by fans and natural convection.
• Mounting SERVOPACKs Side by Side in a Control Panel
• Σ-V Series
Leave sufficient space on each side and at the top and the bottom of each SERVOPACK. The width on each
side varies in accordance with the models of the SERVOPACKs used.
R70F, R90F, 2R1F, R70A, R90A, 1R6A, 2R8A
2R8F, 3R8A, 5R5A, 7R6A
120A, 180A, 200A, 330A, 470A, 550A, 590A, 780A,
1R9D, 3R5D, 5R4D, 8R4D, 120D, 170D, 210D, 260D,
280D, 370D
Also install cooling fans above the SERVOPACKs to disperse local pockets of warmer air around the SERVO-
PACKs.
3-4
Fan
30 mm or more
Width varies with SERVOPACK model.
SERVOPACK Model SGDV-
Fan
40 mm or more
40 mm or more
Side
Left
Right
1 mm or more
1 mm or more 10 mm or more
10 mm or more
Top and Bottom
40 mm or more