Page 1
YASKAWA AC Drive Option Modbus TCP/IP Technical Manual Model SI-EM3D To properly use the product, read this manual thoroughly and retain for easy reference, inspection, and maintenance. Ensure the end user receives this manual. MANUAL NO. SIEP C730600 0E YAI...
YASKAWA products remain the responsibility of the equipment designer or end user. YASKAWA accepts no responsibility for the way its products are incorporated into the final system design. Under no circumstances should any YASKAWA product be incorporated into any product or design as the exclusive or sole safety control.
• The products and specifications described in this manual or the content and presentation of the manual may be changed without notice to improve the product and/or the manual. • Contact Yaskawa or a Yaskawa representative and provide the manual number shown on the front cover to order new copies of the manual. DANGER Do not ignore the safety messages in this manual.
≥ 1011 Refer to “PRG” on the drive nameplate for the software version number. Before you install the option on a YASKAWA AC Drive GA500, GA700, GA800, or HV600, make sure that the option software version is PRG: 0383 or later.
• Make sure that the model number on the option nameplate and the model number on the purchase order are the same. Refer to Figure 4.1 for more information. • Contact the distributor where you purchased the option or contact Yaskawa or a Yaskawa representative about any problems with the option. ◆ Option Package Contents Table 3.1 Contents of Package...
The communication modular connector CN1 on the option is a modular dual RJ45 female connector designated port 1 and port 2. Port 1 and port 2 are the connection points for a customer-supplied male Modbus TCP/IP network communication cable. YASKAWA SIEP C730600 0E YAI Modbus TCP/IP Technical Manual...
Control connection active connection. Communications error (fatal) The option detected a duplicate IP address. Yellow 10 Mbps is established 10/100 Yellow 100 Mbps is established LINK/ACT Green Link is not established YASKAWA SIEP C730600 0E YAI Modbus TCP/IP Technical Manual...
Do not operate a drive or connected equipment that has damaged or missing parts. You can cause damage to the drive and connected equipment. NOTICE Use Yaskawa connection cables or recommended cables only. Incorrect cables can cause the drive or option to function incorrectly. NOTICE Damage to Equipment.
Procedure D To install the option on GA500 drives, use the option mounting kit (JOHB-GA50) and manual. Before you install the option on a YASKAWA AC Drive GA500, make sure that the option software version is PRG: 0383 or later. ■...
Page 13
(D). Use the last remaining included screw (B) to connect the other end of the ground wire (C) to the remaining ground terminal and installation hole on the option (A). Tighten the screws to a correct tightening torque: • 0.5 N∙m to 0.6 N∙m (4.4 in∙lb to 5.3 in∙lb) YASKAWA SIEP C730600 0E YAI Modbus TCP/IP Technical Manual...
Page 14
(ESD) procedures. If you do not follow procedures, it can cause ESD damage to the drive circuitry. Reattach the front cover (A), terminal cover (C), and keypad (B). Refer to the drive manuals for more information. YASKAWA SIEP C730600 0E YAI Modbus TCP/IP Technical Manual...
J - Insertion point for CN5 connector E - Keypad K - Connector CN5 F - LED label Figure 5.8 Drive Components with Option Install the Option Use this procedure to install the option. YASKAWA SIEP C730600 0E YAI Modbus TCP/IP Technical Manual...
Page 16
Put the LED label (B) in the correct position on the drive front cover (A). A - Drive front cover B - LED label Figure 5.10 Put the LED Label on the Drive Front Cover YASKAWA SIEP C730600 0E YAI Modbus TCP/IP Technical Manual...
Page 17
Reattach the drive front cover (A) and the keypad (B). Refer to the drive manuals for more information. NOTICE Do not pinch cables between the front covers and the drive. Failure to comply could cause erroneous operation. YASKAWA SIEP C730600 0E YAI Modbus TCP/IP Technical Manual...
This section shows the procedure to install and wire the option on a GA700 or GA800 drive. Prepare the Drive for the Option Before you install the option on a YASKAWA AC Drive GA700 or GA800, make sure that the option software version is PRG: 0383 or later.
Page 19
Refer to the drive manuals for more information. NOTICE Do not remove the LED Status Ring board cable connector. If you disconnect the LED Status Ring board, it can cause incorrect operation and damage to the drive. YASKAWA SIEP C730600 0E YAI Modbus TCP/IP Technical Manual...
Page 20
Note: • Replace the keypad connector then install the keypad. • Put the keypad connector tab into the holder when you install the keypad connector to the holder. YASKAWA SIEP C730600 0E YAI Modbus TCP/IP Technical Manual...
This section shows the procedure to install and wire the option on an HV600 drive. Prepare the Drive for the Option Before you install the option on a YASKAWA AC Drive HV600, make sure that the option software version is PRG: 0383 or later.
Page 22
Damage to Equipment. When you touch the option, make sure that you observe correct electrostatic discharge (ESD) procedures. If you do not follow procedures, it can cause ESD damage to the drive circuitry. YASKAWA SIEP C730600 0E YAI Modbus TCP/IP Technical Manual...
Page 23
Put the LED label (B) in the correct position on the drive front cover (A). A - Drive front cover B - LED label Figure 5.22 Put the LED Label on the Drive Front Cover YASKAWA SIEP C730600 0E YAI Modbus TCP/IP Technical Manual...
Page 24
Install the option (A) into the CN5 connector (C) on the drive and use one of the included screws (B) to put it in place. Tighten the screw to a correct tightening torque: • 0.5 N∙m to 0.6 N∙m (4.4 in∙lb to 5.3 in∙lb) YASKAWA SIEP C730600 0E YAI Modbus TCP/IP Technical Manual...
Page 25
Figure 5.26 for instruction about crimp terminal orientation (C) and cable wiring route. A - Ground wire C - Crimp terminal B - Included screw Figure 5.26 Connect the Ground Wire YASKAWA SIEP C730600 0E YAI Modbus TCP/IP Technical Manual...
Related Drive Parameters on page 27 for correct option performance. ◆ Communication Cable Specifications Yaskawa recommends using shielded Cat5e cable. The Yaskawa warranty does not cover other cable types. ■ Option Connection Diagram Figure 5.28 Option Connection Diagram Connect the specified ground wire for installations on 1000-series, GA500, and HV600 drives. The ground wire is not necessary for installation on GA700 or GA800 drives.
Set b1-01 = 3 [Frequency Reference Selection 1 = Option PCB] to use the master device to control the frequency reference of the drive. • Settings 7 to 9 are available in HV600 software versions PRG: 1011 and later. YASKAWA SIEP C730600 0E YAI Modbus TCP/IP Technical Manual...
Page 28
1 : Enabled Note: • This parameter is not available in all 1000-series drives. • Changes to this parameter take effect immediately. It is not necessary to cycle power on the drive. YASKAWA SIEP C730600 0E YAI Modbus TCP/IP Technical Manual...
Page 29
Sets the static/fixed Gateway address. Sets the third most significant octet. (03EF) Note: (0 - 255) • This parameter is only effective when F7-13 = 0 [Address Mode at Startup = Static]. YASKAWA SIEP C730600 0E YAI Modbus TCP/IP Technical Manual...
Page 30
(043C) (0, 1) (Function common to 0 : Parameter changes are activated when ENTER command is written communication option) 1 : Parameter changes are activated immediately. No ENTER command is necessary. YASKAWA SIEP C730600 0E YAI Modbus TCP/IP Technical Manual...
7.2, all of the drive command registers have been mapped to this high speed access area (Modbus TCP/IP registers 01 (Hex.) to 01F (Hex.)). In addition, the monitors shown in Table 7.3 are mapped for high speed access. YASKAWA SIEP C730600 0E YAI Modbus TCP/IP Technical Manual...
Page 32
Enables the function in bit 7 bit 6 Fault Relay Output bit 7 Terminal MA/MB-MC (varies by drive model) Reserved bit 8 - F 000A Pulse train output (Units: 1/1 Hz, setting range: 0 - 32000) YASKAWA SIEP C730600 0E YAI Modbus TCP/IP Technical Manual...
Page 33
Output Frequency Monitor (U1-02) 2006 Output Current (U1-03) (units: 0.1 A) 2007 Terminal A2 Input Level Monitor (U1-14) 2008 DC Bus Voltage Monitor (U1-07) Reserved 2009 Error Signal 1 Undervoltage (Uv1) YASKAWA SIEP C730600 0E YAI Modbus TCP/IP Technical Manual...
This is sometimes referred to as the Unit ID. This field is not usually used because the drive with the option does not have a gateway function. Refer to the manual of the master or gateway used when you set the value to the Unit identifier. YASKAWA SIEP C730600 0E YAI Modbus TCP/IP Technical Manual...
Page 38
Data (Hex.) Slave Address (Unit Identifier) 00 - FF Function Code Starting Register 0000 - FFFF Quantity of Registers Number of Data Bytes × 2 Register Values × 2 0000 - FFFF YASKAWA SIEP C730600 0E YAI Modbus TCP/IP Technical Manual...
Page 39
The drive responds the value of register address 0001 (Hex.) to the PLC. Table 7.22 Example Write Multiple Registers Response Description Data (Hex.) Slave Address (Unit Identifier) Function Code Starting Register Upper YASKAWA SIEP C730600 0E YAI Modbus TCP/IP Technical Manual...
Page 40
Table 7.29 shows examples of an error response when the command to read and write to multiple registers has failed. The exception code is 02 (Hex.) (indicating a register number error). YASKAWA SIEP C730600 0E YAI Modbus TCP/IP Technical Manual...
• Control data or parameter write data is outside the allowable setting range. • Attempted to write a contradictory parameter setting. Write Mode Error • Attempted to write while the drive was operating to a parameter that cannot be written to during run. YASKAWA SIEP C730600 0E YAI Modbus TCP/IP Technical Manual...
A valid password is necessary to access. ◆ Home Page The Home page shows the status of the drive and the I/O. It also shows identifying information about the drive and the option. YASKAWA SIEP C730600 0E YAI Modbus TCP/IP Technical Manual...
The time between the last two writes to the Control register, MEMOBUS/Modbus Control Connection Delta Time address 0001 (Hex.). ◆ Network Page The Network tab shows the status of the option network traffic and the status of open I/O connections. YASKAWA SIEP C730600 0E YAI Modbus TCP/IP Technical Manual...
Page 44
Cumulative number of errors for uneven packets lengths. FCS Errors Cumulative number of frame check sequence errors. Single Collisions Cumulative number of single collisions. Multiple Collisions Cumulative number of multiple collisions. YASKAWA SIEP C730600 0E YAI Modbus TCP/IP Technical Manual...
• Output Frequency • Output Current • Motor Speed • Torque Reference • DC Bus Voltage • Terminal Analog Input 1 • Terminal Analog Input 2 • Terminal Analog Input 3 YASKAWA SIEP C730600 0E YAI Modbus TCP/IP Technical Manual...
OR or AND are needed, set the [OR/AND] drop-down selection to [NotUsed]. 3. Enter the email address where the alert will be sent. 4. Enter the message that will appear in the email contents. YASKAWA SIEP C730600 0E YAI Modbus TCP/IP Technical Manual...
Entering a valid password allows access to the settings in the Settings page, Email Alerts page, and the Parameter Access page. ■ Webpage Password To change the password, enter the new password in the [New Password] and [Confirm Password] text boxes. Click [Save password]. YASKAWA SIEP C730600 0E YAI Modbus TCP/IP Technical Manual...
U6-80, U6-81, U6-82, and U6-83. Refer to Table 9.1 for example values of the monitors for an option IP address of 192.168.1.20. Table 9.1 Example IP Address Monitor Values Monitor Value U6-80 U6-81 YASKAWA SIEP C730600 0E YAI Modbus TCP/IP Technical Manual...
• 4022 = Port 1 is discarding and is the alternate port. Port 2 is forwarding and is the root port. • 2260 = Port 1 is forwarding and is the root port. Port 2 is discarding and is the disabled port. YASKAWA SIEP C730600 0E YAI Modbus TCP/IP Technical Manual...
To use other options, refer to those option manuals. An option of the same type is already installed in Connect the option to the correct option port. oFb02 Option Fault option port CN5-A, CN5-B, or CN5-C. YASKAWA SIEP C730600 0E YAI Modbus TCP/IP Technical Manual...
You can connect a maximum of 3 options at the same time depending on the type of option. Note: You can only connect one option to the GA500 and HV600. Connect the option to the CN5 connector. YASKAWA SIEP C730600 0E YAI Modbus TCP/IP Technical Manual...
Figure 11.1 Option Installation for CE Compliance: 1000-Series, GA700, GA800 Figure 11.2 Option Installation for CE Compliance: GA500, HV600 Ground the largest possible surface area of the shield to the metal panel. Use cable clamps if possible. YASKAWA SIEP C730600 0E YAI Modbus TCP/IP Technical Manual...
• Falling foreign objects Up to 1000 m (3280 ft) Altitude Disposal ◆ Disposal Instructions Correctly dispose of the product and packing material as specified by applicable regional, local, and municipal laws and regulations. YASKAWA SIEP C730600 0E YAI Modbus TCP/IP Technical Manual...
The wheelie bin symbol on this product, its manual, or its packaging identifies that you must recycle it at the end of its product life. You must discard the product at an applicable collection point for electrical and electronic equipment (EEE). Do not discard the product with usual waste. YASKAWA SIEP C730600 0E YAI Modbus TCP/IP Technical Manual...
Revision History Date of Publication Revision Number Section Revised Content May 2021 Updated instructions to support YAI software. June 2020 First Edition YASKAWA SIEP C730600 0E YAI Modbus TCP/IP Technical Manual...
Page 58
Phone: +81-3-5402-4502 Fax: +81-3-5402-4580 www.yaskawa.co.jp YASKAWA AMERICA, INC. 2121, Norman Drive South, Waukegan, IL 60085, U.S.A. Phone: +1-800-YASKAWA (927-5292) or +1-847-887-7000 Fax: +1-847-887-7310 www.yaskawa.com YASKAWA ELÉTRICO DO BRASIL LTDA. 777, Avenida Piraporinha, Diadema, São Paulo, 09950-000, Brasil Phone: +55-11-3585-1100 Fax: +55-11-3585-1187 www.yaskawa.com.br...