Status Bar; Figure 36: Status Messages In The Application Window Of The Parameterization Dialog; Figure 37: Status Bar In The Parameterization Dialog; Table 43: Status Messages - Possible Status Messages With Additional Information - WAGO 750-486/040-000 Manual

4ai 0/4-20ma ne43 ex i xtr 4-channel analog input; 0/4...20 ma; ne43; intrinsically safe; extreme for wago-i/o-system 750 xtr
Table of Contents

Advertisement

WAGO-I/O-SYSTEM 750 XTR
750-486/040-000 4AI 0/4-20mA NE43 Ex i XTR
The following status messages with corresponding additional information are
displayed:
Table 43: Status Messages – Possible Status Messages with Additional Information
Status message
Measurement range overflow
Measurement range underflow
User-defined limiting value
overrange
User-defined limiting value
underrange
Short circuit
Wire break
Channel deactivated
Measured values in permissible
range
The status messages are displayed with assignment of the relevant I/O module
channels.

Figure 36: Status Messages in the Application Window of the Parameterization Dialog

2.
Click the [Delete] button to clear the status message history. The history is
automatically cleared if you interrupt the connection to the I/O module or
close the parameterization dialog.
7.1.1.7

Status Bar

The following information is displayed in the status bar:
Status indication with display of the currently executed action as text or the
respective error message if an error occurs
A progress bar is displayed as the actions are executed
Online status
IP address or COM interface

Figure 37: Status Bar in the Parameterization Dialog

Error type
Channel
Warning
x
Warning
x
Warning
x
Warning
x
Error
x
Information
x
Error
x
Information
x
Information
x
Information
x
Commissioning
77
Status byte
0x42
0x41
0x04
0x08
0x50
0x00
0x60
0x00
0x00
0x00
Manual