Diagnostics; Table 24: Overview Of The Diagnostics And Status Messages Of The - WAGO 753-1630 Manual

Smi master module 230 v ac
Table of Contents

Advertisement

60

Diagnostics

Pos: 106 /Alle Serien (Allgemeine Module)/Überschriften/Ebene 1/Diagnose - Überschrift 1 @ 4\mod_1240831069471_21.docx @ 31372 @ 1 @ 1
9
Diagnostics
Pos: 107 /Serie 753 (WAGO-I/O-SYSTEM)/Diagnose/Diagnose 753-1630, -1631 @ 27\mod_1471869783513_21.docx @ 218855 @ @ 1
The behavior of the SMI master module if a diagnostic is present depends on the
configuration. The diagnostics can be globally activated or deactivated in the
WAGO SMI Configurator and via IEC function blocks.
The diagnostic function is activated by default.
If there is a diagnostic, the SMI master module displays a general error.
Depending on the detected diagnostic, maximum one corresponding status but
can also be set. Therefore, the diagnostics have a prioritization. If there are
multiple errors, the diagnostic with the higher prioritization is displayed (see also
section "Process Image" > "Status Byte").
The SMI master module provides diagnostics for the following events:
• Controller failure
• Forced position active
• Undervoltage field supply
• Short circuit of SMI connections
In addition to the diagnostics, the SMI master outputs non-deactivatable status
messages in process data communication via a bit in the extended status byte to
the following events:
• Energy saving mode active
• Controller locking active
• Status of the digital input
The table below shows the statuses of the SMI master module with possible
diagnostics and status messages.
Table 24: Overview of the Diagnostics and Status Messages of the SMI Master Module
Status bit 6
(general error)
1
1
1
1
0
0
0
Manual
Version 1.2.0 FW/HW Version 02/01
Status byte
Set bit
Bit 3
Bit 4
753-1630 SMI Master Module 230 V AC
Extended
status byte
Set bit
Undervoltage field supply
Short circuit of SMI connections
Bit 0
Forced position active
Bit 1
Energy saving mode active
Bit 2
Controller locking active
Bit 8
Status of the digital input
Diagnostics
Controller failure

Advertisement

Table of Contents
loading

This manual is also suitable for:

I/o system 750 seriesI/o system 750/753753-1631

Table of Contents