4.1.1.6.2 Parameter Vibration Monitoring (RMS)
The following parameters can be defined for each channel for the vibration
monitoring:
·
·
·
·
·
4.1.1.6.3 Parameter Roller Bearing Monitoring (SPM)
The following parameters can be defined for each channel for the roller
bearing monitoring:
·
·
·
·
·
WAGO-I/O-SYSTEM 750
I/O-Modules
Lower limiting frequency (2 Hz or 10 Hz)
Alarm threshold (0 mm/s ... measuring range end value)
Warning threshold (0 mm/s ... measuring range end value)
Delay time alarm (0 ... 600 s)
Delay time warning (0 ... 600 s)
Measuring range end value (40 dBSV, 60 dBSV, 80 dBSV)
Alarm threshold (-10 dB
Warning threshold (-10 dB
Delay time alarm (0 ... 600 s)
Delay time warning (0 ... 600 s)
750-645 [2AI/2DO VIB VRMS/SPM Multi]
... measuring range end value)
SV
... measuring range end value)
SV
Function Description