Verifying Level Condition

Required tools: digital level
1
In the control module only, verify the system unit is level front to back and left to right by placing the
digital level at the following locations:
a. Inside the access door
b. On the left side inside the access door
A reading on the digital level that is 0.00 +/- 0.30 is to be considered level.
Make sure the digital level is not resting on any frame welds or debris that
Note
would cause an inaccurate reading. To find the small circular frame welds,
run your finger tips over the spot where you are going to place the level
placements of level
If the module does not meet the 0.00 +/- 0.30 leveling requirement, go to
34.
If the module is sufficiently level, go to
Scalar i6000 Installation Guide
Lowering All Other Leveling Legs
Additional Leveling
on page
on page 35.