The instructions in this chapter tell you how to apply power to a library. Before applying power, you should
perform a voltage check. The information in this chapter includes:

Supported AC Power Cables

Powering on the Library
Supported AC Power Cables
Each library is configured with a single AC power source, but redundant power is an option. If redundant
power is chosen, the control module and all expansion modules that contain tape drives require two
independent AC power sources.
You must install your library with two independent power sources to
CAUTION
have redundant power. You will NOT have redundant power if you use
only one AC power source.
The power cable length for each of these inputs is 14 feet (4.26 m). See
Table 2
Electrical Specifications for Control and Expansion Modules
Voltage (Single
Location
Phase, 50 - 60 Hz)
North America
110
North America
208
International
240
a. 20 amps in North America
b. 16 amps international
Scalar i6000 Installation Guide
on page 93
on page 94
Required Protective
Service
30
15
16

Applying Power

Table 2
on page 93.
Delivered Power
AMPs
Connector
NEMA L5 - 30
30
NEMA L6 - 15
15
IEC60309 2P+E
20
a
b
or 16