9 Monitoring and Setting Using the Modbus TCP Devices
9-3-2

Setting Information

 Comprehensive current diagnosis type (K6CM-CI2M)
Address
Parameter name
A000 hex
Display value
type
A001 hex
Trigger mode
A002 hex
Trigger type
A003 hex
Trigger level
A004 hex
Monitoring time
A005 hex
Alarm latch
A006 hex
Use Running
Time
A007 hex
Moving average
times
9 - 12
Description
Sets which measurement value is dis-
played in the 7 segment display on the
front of the K6CM device.
0: PV (Present value)
1: MIN
2: MAX
Selects the trigger mode.
0: Free run
1: External trigger
2: Internal trigger
Set the trigger measurement start condi-
tion. Setting is not required when the
trigger mode is "Free run".
0: Rising edge
1: Falling edge
2: Level
For "Internal trigger", set the measure-
ment value to start trigger measurement.
Setting is not required when the trigger
mode is "Free run" or "External trigger".
Note : Unit and decimal point position
follow measurement values.
(Refer to A-6 Internal Data of
K6CM Devices on page A-14.)
Sets the monitoring time.
1 to 6000 (unit: 0.1 seconds)
(0001 to 1770 hex)
Sets enable/disable of alarm latch func-
tion.
0: Disable (no latch)
1: Enable (with latch)
Set the function to detect the life of the
K6CM device.
0: OFF (not used)
1: ON (use)
Every time the measurement value is
sampled, the data of the past n times
including the sampling data of that time
is averaged.
0: OFF
1: 2 times
2: 4 times
3: 8 times
4: 16 times
5: 32 times
K6CM Motor Condition Monitoring Device User's Manual (N219)
Number
*1
R/W
of bytes
2
R/W
0000 hex
2
R/W
0000 hex
2
R/W
0000 hex
2
R/W
0000 hex
2
R/W
0001 hex
2
R/W
0001 hex
2
R/W
0000 hex
2
R/W
0003 hex
Initial
value