Setting Switch; How To Use Setting Switches - Omron KM1 User Manual

Smart power monitor
Table of Contents

Advertisement

0BOverview

Setting switch

DIP switches and a rotary switch are used for setting switches. DIP switches select communication
protocols, while a rotary switch sets a slave ID. When multiple units are connected, slave IDs are
used to identify the units. (A rotary switch is used only for functional slaves and CT extension slaves.
The slave for measurement master will have a fixed ID of 0. )
DIP switch
No.1 ⇒ Idle
No.2 ⇒ Selection of communication protocol:
Rotary switch
Set a slave ID.
0

How to use setting switches

Be sure to use the switch when the power supply is turned OFF. The settings will be read
only when connected to a power supply and any change made during power distribution will
not be reflected. To make change, switch off the power first and change the settings. And
switch on the power again.
When selecting a switch, set it to the specified position securely by using a small flat-head
screwdriver.
1-8
OFF CompoWay/F
ON Modbus
:
Do not use the IDs of 0 and 6-9. )
* For slave units, set slave ID of 1-4. For EMU8A
(pulse/temperature) to be used for the 3-STATE
function or power original unit, however, set slave ID
to 5.
* If multiple units are connected, set slave IDs in a way
to avoid duplicates.