Omron K6CM User Manual page 172

Motor condition
Hide thumbs Also See for K6CM:
Table of Contents

Advertisement

6 How to Use the Motor condition monitoring Tool
Parameter name
Moving average
times
Circuit topology
Using inverter
Inverter special
measurement
Insulation resis-
tance failure warn-
ing
Insulation resis-
tance failure critical
Transistor output
method
Monitoring delay
time
6 - 22
Setting range
0: OFF
1: 2 times
2: 4 times
3: 8 times
4: 16 times
5: 32 times
0: Three-phase three-wire sys-
tem, S-phase grounding
1: Three-phase four-wire system,
N-phase grounding, delta con-
nection load
0: OFF
1: ON
0: OFF
1: ON
0.000 to 9.999
0.000 to 9.999
0: Normally Close
1: Normally Open
0.0 to 600.0 seconds
Description
Every time the measurement value is sam-
pled, the data of the past n times including the
sampling data of that time is averaged.
(n is the moving average number on the
shown left column.)
Set the circuit topology according to the distri-
bution method of the equipment to be moni-
tored.
Set according to the presence or absence of
the inverter of the equipment to be monitored.
Set according to the inverter frequency setting
of the equipment to be monitored.
Set a threshold value for outputting individual
alarm warning of the insulation resistance.
Set a threshold value for outputting individual
alarm critical of the insulation resistance.
Select transistor output method.
Set the delay time from the trigger input to the
start of measurement.
K6CM Motor Condition Monitoring Device User's Manual (N219)
Default
0: OFF
0: Three-phase
three-wire system,
S-phase grounding
0: OFF
0: OFF
0.800
0.400
0
0.0