Address
Parameter name
A008 hex
Current range
A009 hex
Reserved area
A00A hex
Reserved area
A00B hex
Current failure
warning
A00C hex
Current failure
critical
A00D hex
Degradation level
1 failure warning
A00E hex
Degradation level
1 failure critical
A00F hex
Degradation level
2 failure warning
A010 hex
Degradation level
2 failure critical
A011 to
Reserved area
A012 hex
A013 hex
Transistor output
method
A014 hex
Monitoring delay
time
K6CM Motor Condition Monitoring Device User's Manual (N219)
9 Monitoring and Setting Using the Modbus TCP Devices
Description
Sets the current range.
0: 5 A
1: 25 A
2: 100 A
3: 200 A
4: 400 A
5: 600 A
Reserved area
Reserved area
Sets the current failure warning thresh-
old.
0 to 9999
(Unit in the 5 A range: 0.01 A)
(Unit in other ranges: 0.1 A)
(0000 to 270F hex)
Sets the current failure critical threshold.
0 to 9999
(Unit in the 5 A range: 0.01 A)
(Unit in other ranges: 0.1 A)
(0000 to 270F hex)
Sets the degradation level 1 failure
warning threshold.
0 to 9999
(0000 to 270F hex)
Sets the degradation level 1 failure criti-
cal threshold.
0 to 9999
(0000 to 270F hex)
Sets the degradation level 2 failure
warning threshold.
0 to 9999
(0000 to 270F hex)
Sets the degradation level 2 failure criti-
cal threshold.
0 to 9999
(0000 to 270F hex)
Reserved area
Select transistor output method.
0: Normally Close
1: Normally Open
Set the delay time from the trigger input
to the start of measurement.
0.0 to 6000 (unit: 0.1 seconds)
(0000 to 1770 hex)
Number
*1
R/W
of bytes
2
R/W
0003 hex
2
R/W
0000 hex
2
R/W
0000 hex
2
R/W
07D0 hex
(2000)
2
R/W
07D0 hex
(2000)
2
R/W
001E hex
(30)
2
R/W
0032 hex
(50)
2
R/W
0014 hex
(20)
2
R/W
0032 hex
(50)
2
R/W
0000 hex
2
R/W
0000 hex
2
R/W
0000 hex
Initial
value
9
9 - 13