Omron K6CM User Manual page 209

Motor condition
Hide thumbs Also See for K6CM:
Table of Contents

Advertisement

Attri-
Parameter
bute ID
name
67 hex
Trigger mode
68 hex
Trigger type
69 hex
Trigger level
6A hex
Monitoring
time
6B hex
Alarm latch
6C hex
Use Running
Time
6D hex
Moving aver-
age times
A0 hex
Transistor out-
put method
A1 hex
Monitoring
delay time
*1. If you execute the software reset after writing to the attribute ID 65 to 78 hex or A0 to A4 hex, wait for about 1
second, considering the time until these setting values are saved, and then execute the software reset.
*2. If this attribute is set when using K6CM-CI2M, the value is set for both attribute ID A2 hex (current moving
average times) and attribute ID A3 hex (degradation level 1 moving average times) at the same time.
K6CM Motor Condition Monitoring Device User's Manual (N219)
8 Monitoring and Setting Using the EtherNet/IP Devices
Description
Selects the trigger mode.
0: Free run
1: External trigger
2: Internal trigger
Set the trigger measurement start condition. Set-
ting is not required when the trigger mode is "Free
run".
0: Rising edge
1: Falling edge
2: Level
For "Internal trigger", set the measurement value
to start trigger measurement.
Setting is not required when the trigger mode is
"Free run" or "External trigger".
Note : Unit and decimal point position follow
measurement values. (Refer to A-6 Inter-
nal Data of K6CM Devices on page A-14.)
Sets the monitoring time.
1 to 6000 (unit: 0.1 seconds)
(0001 to 1770 hex)
Sets enable/disable of alarm latch function.
0: Disable (no latch)
1: Enable (with latch)
Sets the usage or nonuse of K6CM remaining
capacity function.
0: OFF (not used)
1: ON (use)
Every time the measurement value is sampled, the
data of the past n times including the sampling
data of that time is averaged.
0: OFF
1: 2 times
2: 4 times
3: 8 times
4: 16 times
5: 32 times
Select transistor output method.
*3
0: Normally Close
1: Normally Open
Set the delay time from the trigger input to the start
of measurement.
*4
0.0 to 6000 (unit: 0.1 seconds)
(0000 to 1770 hex)
Attri-
bute
Write
Write
Write
Write
Write
Write
Write
*2
Write
Write
Data
Data
Default value
type
UINT
0000 hex
UINT
0000 hex
UINT
0000 hex
UINT
0001 hex (1)
(Unit: 0.1 sec-
onds)
UINT
0001 hex
UINT
0000 hex
UINT
Comprehen-
sive current
diagnosis type:
0003 hex
Vibration &
temperature
type, Insulation
resistance type:
0000 hex
UINT
0000 hex
UINT
0000 hex
8 - 19
8

Advertisement

Table of Contents
loading

This manual is also suitable for:

K6cm-ismK6cm-cimK6cm-vbmK6cm-ci2m