8 Monitoring and Setting Using the EtherNet/IP Devices
 Vibration & temperature type (K6CM-VBM)
Attri-
Parameter
bute ID
name
6E hex
Temperature
unit
6F hex
Reserved
area
70 hex
Reserved
area
71 hex
Acceleration
failure warning
72 hex
Acceleration
failure critical
73 hex
Velocity fail-
ure warning
74 hex
Velocity fail-
ure critical
75 hex
Motor tem-
perature fail-
ure warning
76 hex
Motor tem-
perature fail-
ure critical
77 hex
Temperature
gap failure
warning
78 hex
Temperature
gap failure
critical
8 - 22
Description
Sets the temperature unit.
0: °C
1: °F
Reserved area
Reserved area
Sets the acceleration failure warning
threshold.
0 to 9999 (Unit: 0.01 G)
(0000 to 270F hex)
Sets the acceleration failure critical
threshold.
0 to 9999 (Unit: 0.01 G)
(0000 to 270F hex)
Sets the velocity failure warning threshold.
0 to 9999 (Unit: 0.01 mm/s)
(0000 to 270F hex)
Sets the velocity failure critical threshold.
0 to 9999 (Unit: 0.01 mm/s)
(0000 to 270F hex)
Sets the motor temperature failure warn-
ing threshold.
0 to 9999 (Unit: °C)
(0000 to 270F hex)
Sets the motor temperature failure critical
threshold.
0 to 9999 (Unit: °C)
(0000 to 270F hex)
Sets the temperature gap failure warning
threshold.
0 to 9999 (Unit: °C)
(0000 to 270F hex)
Sets the temperature gap failure critical
threshold.
0 to 9999 (Unit: °C)
(0000 to 270F hex)
K6CM Motor Condition Monitoring Device User's Manual (N219)
Data
Attri-
bute
Data type
Default value
Write
UINT
0000 hex
Write
UINT
0000 hex
Write
UINT
0000 hex
Write
UINT
0032 hex (50)
Write
UINT
0064 hex (100)
Write
UINT
0FA0 hex
(4000)
Write
UINT
1194 hex
(4500)
Write
UINT
0050 hex (80)
Write
UINT
0050 hex (80)
Write
UINT
0050 hex (80)
Write
UINT
0050 hex (80)