Omron K6CM User Manual page 307

Motor condition
Hide thumbs Also See for K6CM:
Table of Contents

Advertisement

Appendices
The timeout time when a communication error occurs can be calculated as follows.
Timeout time = RPI (ms) × multiple of RPI set by timeout value (4 times, 8 times, 16 times,
..., 512 times)
This completes the tag data link setting. Go online to the originator device (PLC) and down-
load the EtherNet/IP tag data link settings to the PLC by clicking [Transfer to Controller]
Button.
A
(The EtherNet/IP tag data link communications setting of the K6CM series is fixed, so you
do not need to download it to the K6CM.)
A - 47
K6CM Motor Condition Monitoring Device User's Manual (N219)