*2. Measurement status (common form of measurement values)
The measurement status is handled as 2-byte data consisting of bit data in the table.
Example: The individual alarm result (Warning) is "ON".
The 12th bit is "1", so it is "0001 0000 0000 0000" in binary notation and "1000" in hexadecimal notation.
In the log file (CSV) of the Motor condition monitoring tool, the Main body status is in hexadecimal notation.
Bit position
00
01
02
03
04
05
06
07
08
09
10
11
12
13
14
15
Precautions for Correct Use
If the trigger mode is "Free run (no trigger), read the data when "Present value not measured"
bit (bit 00) of the measurement status is 0.
There is a possibility that the value before monitoring (i.e., 0) is being read.
K6CM Motor Condition Monitoring Device User's Manual (N219)
8 Monitoring and Setting Using the EtherNet/IP Devices
Status
Present value unmeasured state
Present value input error
Reserved area
Reserved area
Maximum value unmeasured state
Maximum value input error
Reserved area
Reserved area
Minimum value unmeasured state
Minimum value input error
Reserved area
Reserved area
Individual alarm result (Warning)
Individual alarm result (Critical)
Reserved area
Reserved area
Bit contents
0
Measured
Standby
Not occurred
Occurrence
Measured
Standby
Not occurred
Occurrence
Measured
Standby
Not occurred
Occurrence
OFF
ON
OFF
ON
1
8
8 - 11