Omron K6CM User Manual page 266

Motor condition
Hide thumbs Also See for K6CM:
Table of Contents

Advertisement

Appendices
Item
Indicators
External trigger input
Transistor output
Ambient operating temperature
humidity
Storage ambient temperature
Storage humidity
Altitude
Recommended fuse (input)
Insulation resistance
Dielectric strength
Vibration resistance
Shock resistance
Degree of protection
Warranty period
Terminal type
Exterior color
Applicable standards
Mounting
Weight
A - 6
MS: red / green, NS: red / green, alarm bar: green / yellow / red
No-voltage contact and open collector are possible.
Short circuit: Residual voltage 1.5 V or less
Open: Leakage current 0.1 mA or less
Short circuit current: approx. 7 mA
Minimum trigger time: 0.1 s
Contact configuration: NPN open collector
Rated voltage: 24 VDC (maximum voltage: DC 26.4 V)
Maximum current: 50 mA
Leakage current: 0.1 mA max.
Residual voltage: 1.5 V max.
-10 to 55 °C (with no condensation or freezing)
25 to 85% (with no condensation)
-20 to 65 °C (with no condensation or freezing)
25 to 85% (with no condensation)
2,000 m max.
UL R/C, CSA Component Acceptance, FIH250V2A, NIPPON SEISEN CABLE LTD
20 MΩ min.
Between all external terminals and the case
Between all power supply terminals and all other terminals
Between all sensor connection terminals and trigger input terminal + output terminal
+ LAN port + all FG terminals
2,000 VAC for 1 minute
Between all external terminals and the case
Between all power supply terminals and all other terminals
Between all sensor connection terminals and trigger input terminal + output terminal
+ LAN port + all FG terminals
Frequency: 10 to 55 Hz, 0.35-mm single amplitude, acceleration 50 m/s
10 sweeps of 5 min each in X,Y, and Z directions
2
100 m/s
, 3 times each in X, Y, and Z axes, 6 directions
IP20
1 year
Push-In Plus
Black (Munsell N 1.5)
Compliance standard:
EN 61010-2-030
Installation environment: overvoltage category II, measurement category II (CAT II
CT input, ZCT (IRT) input), pollution degree 2 (according
to EN 61010-030)
EMC:
EN 61326 - 1 (EMI: Class A EMS: Indutrial Location)
Acceleration:
± 0.1 G, velocity: ± 2.25 mm/s, temperature: ± 6°C, insu-
lation resistance: ± 35% rdg, current: ± 10% F. S.
Safety standards:
UL 61010-2-030 (Listing), Korean Radio Law, RCM
DIN Rail mounting, or screw mounting
Approx. 200 g
K6CM Motor Condition Monitoring Device User's Manual (N219)
Specifications
2

Advertisement

Table of Contents
loading

This manual is also suitable for:

K6cm-ismK6cm-cimK6cm-vbmK6cm-ci2m

Table of Contents