Trigger Mode - Omron K6CM User Manual

Motor condition
Hide thumbs Also See for K6CM:
Table of Contents

Advertisement

3-2-4

Trigger Mode

Trigger is a function of updating and monitoring the measurement values when certain conditions are
met. To observe the aging of the motor, it is necessary to set the installation state, load, and rotation
speed of the motor during measurement to the same condition, and to measure the motor rotating at a
constant speed avoiding the state where the motor is stopped or accelerating or decelerating. Depend-
ing on the application, select the trigger mode from Free run (while power is ON), External Trigger, or
Internal Trigger. The operation of each trigger mode is shown in the table below.
Start condition
Trigger
mode
and monitoring
All times after
Free run
turning ON the
(while power
power of the
is ON)
K6CM device
Depends on exter-
nal conditions
External trig-
ger
Depends on the
relationship
between the mea-
surement value
and the set value
(trigger level)
Internal trig-
*1
ger
*1. The measurement values which can be set the trigger level are as follows.
• Comprehensive current diagnosis type: Current
• Vibration & temperature type: Acceleration
• Insulation resistance type: Insulation resistance
When you select the trigger mode from External trigger or Internal trigger, set the measurement start condi-
tion and end condition by selecting the trigger type.
K6CM Motor Condition Monitoring Device User's Manual (N219)
of measuring
Rising edge
Monitoring time
ON
Measuring and
monitoring
OFF
• Start condi-
When the external trigger
tion
input changes from OFF to
ON
• End condi-
After the monitoring time
tion
has elapsed
Monitoring time
Set
value
Measuring and
monitoring
• Start condi-
When the measurement
tion
value exceeds the set
value (trigger level)
• End condi-
tion
After the monitoring time
has elapsed
3 Measuring and monitoring System
Trigger type
Falling edge
Always measuring
Monitoring time
ON
ON
Measuring and
monitoring
OFF
OFF
When the external trigger
input changes from ON to
While the external input is in
OFF
the ON state
After the monitoring time
has elapsed
Monitoring time
Set
Set
value
value
Measuring and
monitoring
When the measurement
While the measurement
value falls below the set
value exceeds the set value
value (trigger level)
(trigger level)
Note : For the insulation
After the monitoring time
has elapsed
Level
3
Measuring and
monitoring
Measuring and
monitoring
resistance, this is
while present value
falls below the set
value.
3 - 5

Advertisement

Table of Contents
loading

This manual is also suitable for:

K6cm-ismK6cm-cimK6cm-vbmK6cm-ci2m

Table of Contents