9 Monitoring and Setting Using the Modbus TCP Devices
Address
Parameter name
A015 hex
Current moving
average times
A016 hex
Degradation level
1 moving average
times
A017 hex
Degradation level
2 moving average
times
*1. R: Read using Reading of multiple registers (03 hex).
W: Write using writing of multiple registers (10 hex).
 Vibration & temperature type (K6CM-VBM)
Parameter
Address
A000 hex
Display value
type
A001 hex
Trigger mode
A002 hex
Trigger type
A003 hex
Trigger level
9 - 14
Set the current moving average times.
0: OFF
1: 2 times
2: 4 times
3: 8 times
4: 16 times
5: 32 times
Set the degradation level 1 moving aver-
age times.
0: OFF
1: 2 times
2: 4 times
3: 8 times
4: 16 times
5: 32 times
Set the degradation level 2 moving aver-
age times.
0: OFF
1: 2 times
2: 4 times
3: 8 times
4: 16 times
5: 32 times
name
Sets which measurement value is displayed in the
7 segment display on the front of the K6CM device.
0: PV (Present value)
1: MIN
2: MAX
Selects the trigger mode.
0: Free run
1: External trigger
2: Internal trigger
Set the trigger measurement start condition. Set-
ting is not required when the trigger mode is "Free
run".
0: Rising edge
1: Falling edge
2: Level
For "Internal trigger", set the measurement value to
start trigger measurement. Setting is not required when
the trigger mode is "Free run" or "External trigger".
Note : Unit and decimal point position follow
measurement values. (Refer to A-6 Inter-
nal Data of K6CM Devices on page A-14.)
Description
Description
K6CM Motor Condition Monitoring Device User's Manual (N219)
Number
*1
R/W
of bytes
2
R/W
0000 hex
2
R/W
0003 hex
2
R/W
0000 hex
Number
*1
R/W
of bytes
2
R/W
0000 hex
2
R/W
0000 hex
2
R/W
0000 hex
2
R/W
0000 hex
Initial
value
Initial
value