Omron K6CM User Manual page 128

Motor condition
Hide thumbs Also See for K6CM:
Table of Contents

Advertisement

5 Installation and Wiring
Mounting Vibration Sensor Head Easily
For the K6CM-VBS1 (M6 × 8 mm), a magnet for easy-mounting of the sensor is included.
The easy-mounting magnet is used for positioning of measuring place. Note that measurement accu-
racy is not guaranteed in the case of magnet mounting.
The connection between the pre-amplifier and the sensor head is a connector connection.
Fixing the Vibration Sensor Head
Mount the sensor head on the shaft side exterior of the induction motor.
Mount the vibration sensor head vertically to the upper shaft side of the motor
Load side
There are two ways to mount the vibration sensor head to the motor.
Method
Method 1: Screw Mounting (recom-
mended)
Method 2: Adhesive Mounting (
*1. K6CM will not conform to safety standards if attaching the vibration sensor with adhesive. In the case of dis-
connection, take safety measures such as fixing the cables.
We recommend Method 1 with a good absolute accuracy. However, if you cannot tap the motor, use
Method 2.
5 - 8
Sensor Easy mounting magnet
23-mm dia.
Note: The Sensor Easy mounting
magnet is similar in shape to an
adhesive attachment. Be careful
not to handle it by mistake.
Three-phase induction motor
At the top of the armor of the motor, cut the tap into which the M6 screw
vertically enters, and screw the vibration sensor head into it.
*1
Secure the attachment which is sold separately to the exterior of the
)
motor using adhesive. Screw the vibration sensor head into the fixed
attachment.
K6CM Motor Condition Monitoring Device User's Manual (N219)
Description