 Setting switch
DIP switches and a rotary switch are used for setting switches. DIP switches select communication
protocols, while a rotary switch sets a slave ID. When multiple units are connected, slave IDs are
used to identify the units. (A rotary switch is used only for functional slaves and CT extension slaves.
The slave for measurement master will have a fixed ID of 0. )
DIP switch
No.1  Idle
No.2  Selection of communication protocol:
Rotary switch
Set a slave ID.
0
* For information on Model KM1 series, refer to "Model KM1 User's Manual" (KANC-701).
* For information on the communication slave (DRT (DeviceNet)), refer to Model KE1 DeviceNet
Communication Unit User's Manual" (SGTE-718).
 How to use setting switches
Be sure to use the switch when the power supply is turned OFF. The settings will be read
only when connected to a power supply and any change made during power distribution will
not be reflected. To make change, switch off the power first and change the settings. And
switch on the power again.
When selecting a switch, set it to the specified position securely by using a small flat-head
screwdriver.
OFF CompoWay/F
ON Modbus
:
Do not use the IDs of 0 and 6-9. )
* The slave ID 5 setting is available in Model
KM1-EMU8A-FLK only. Do not use the setting in
Model KE1 series.
* If multiple units are connected, set slave IDs in a way
to avoid duplicates.